What size heat pump do I need? Using the calculator
- 1Choose the whole home or one room, then enter the heated floor area (or the room's length and width) and the ceiling height.
- 2Pick how well the home is insulated — by the year it was built, or by what has been insulated since.
- 3Choose the indoor temperature and the design temperature where you live, or enter your own.
- 4Switch on hot water if the heat pump will heat that too, and read the size in kW, BTU/h and tons.
Heat pump sizing formula: heat loss from floor area and temperature
- 01Temperature difference = indoor temperature − outdoor design temperature
- 02Heat loss (W) = floor area × heat loss per m² per degree × (ceiling height ÷ 2.5 m) × temperature difference
- 03Heat loss per m² per degree = rule-of-thumb W/m² at −10 °C ÷ 30
- 04Heat pump size = heat loss + people × hot-water allowance
- 05BTU/h = W × 3.412; tons = BTU/h ÷ 12,000
Installers in Germany and the Netherlands start a heat pump estimate with a figure per m² of floor: about 40 W/m² for a new home, 60–100 W/m² for a partly insulated one and 100–160 W/m² for an old home without insulation (Bundesverband Wärmepumpe; Bosch). Those figures are for their climate — about −10 °C outside and 20 °C inside, a 30-degree difference — and for rooms about 2.5 m high. The calculator divides them by 30 to get the loss per degree, then multiplies by your own temperature difference and ceiling height, so the same home needs less in London (−3 °C) and more in Chicago (−20 °C).
The design temperature is not the coldest night on record but the cold the heating must still beat on all but a few hours a year: the UK figures (CIBSE Guide A, used by MCS) and the US ones (ASHRAE) are the temperatures that 99.6 % of the hours in a year are warmer than. A heat pump that covers the heat loss at that temperature keeps the home warm nearly all the time without a big backup heater.
Heat pump size example
A partly insulated 1,800 ft² home with 8 ft ceilings, kept at 70 °F inside where the design temperature is 14 °F (New York or Philadelphia), works with a 55.8 °F temperature difference.
It loses about 46,582 BTU/h at that temperature — 25.9 BTU/h per ft², or 3.88 tons (AC) — so it needs a heat pump that still gives that much heat at 14 °F.
Tips before you buy
- Insulate and draught-proof first: every watt per m² you save makes the heat pump smaller and cheaper to run.
- Check your radiators: a heat pump heats the water less hot than a boiler, so some rooms may need bigger radiators or underfloor heating.
- If you heat with gas or oil now, a year of bills is a good cross-check — an installer can work back from it to the heat loss.
- Ask for the room-by-room heat-loss calculation in writing and compare its total with this estimate.
Frequently asked questions
What size heat pump do I need for my house?
Floor area × heat loss per m² per degree × the difference between inside and the design temperature. A partly insulated 120 m² home kept at 20 °C needs about 9.7 kW where the design temperature is −10 °C (the Netherlands, much of Germany) and about 7.5 kW at −3 °C (London). A partly insulated 1,800 ft² home at 70 °F in New York (14 °F) needs about 46,600 BTU/h — close to 4 tons.
How many watts of heat pump per m² or per ft²?
At about −10 °C outside: roughly 40 W/m² for a new home, 60–100 W/m² partly insulated and 100–160 W/m² for an old home without insulation (Bundesverband Wärmepumpe) — about 13, 19–32 and 32–51 BTU/h per ft². Milder places need less and colder ones more; the calculator scales it to your design temperature.
What is the design temperature for a heat pump?
The cold the heating must still cope with. Examples: London −3.0 °C, Birmingham −5.1 °C and Glasgow −5.6 °C (MCS, from CIBSE Guide A); the Netherlands −10 °C (ISSO 51); Berlin about −11 to −13 °C (DIN/TS 12831-1); New York 12.8 °F, Chicago −5 °F and Minneapolis −14.9 °F (ASHRAE, 99.6 %).
Should I add hot water to the heat pump size?
If the heat pump also heats a hot-water cylinder, German planners add about 0.25 kW per person — 1 kW for a family of four. With an electric shower or a separate water heater, leave it out.
Is a bigger heat pump better?
No. A heat pump that is much too big switches on and off often and runs less efficiently. MCS asks for one that covers 100 % of the calculated heat loss at the design temperature; choose a model whose output at that temperature is just above your figure.
Sources
- MCS Heat Load Calculator – external design temperatures from CIBSE Guide A (2015), 99.6 %: London −3.0 °C, Birmingham −5.1, Manchester −4.5, Edinburgh −5.4, Glasgow −5.6, Belfast −3.2, Cardiff −3.1, Leeds −3.3; living rooms 21 °C
- MCS – MIS 3005-D, the heat pump design standard
- MCS – MIS 3005-D clause 5.5: the heat pump should provide at least 100 % of the calculated heat loss
- 42watt – Bundesverband Wärmepumpe, Leitfaden Wärmepumpendimensionierung (11/2025): 30–50 W/m² new or renovated, 60–100 partly renovated, 100–160 unrenovated before 1977
- Bosch Home Comfort – rules of thumb 40 W/m² new build, 75 around 2000, 160 around 1970, and why they usually come out too high
- Passipedia (Passive House Institute) – a passive house has a heating load of at most 10 W/m²
- Bundesverband Wärmepumpe – climate map, design temperature by postcode (DIN/TS 12831-1)
- heiznorm.de – DIN/TS 12831-1 design temperatures by city: Berlin −11.1 to −13.3 °C, Hamburg −8.2 to −10.5, Munich −11.1 to −13.9, Cologne −7.0 to −8.7, Frankfurt −8.3 to −10.1, Dresden −12.1 to −14.0
- ISSO 51 (2017) sample heat-loss calculation – base design temperature −10 °C for the Netherlands
- FGIA – ASHRAE 99.6 % heating design temperatures, US cities (2005 Handbook): New York 12.8 °F, Philadelphia 11.6, Washington 15.9, Boston 7.7, Chicago −5.0, Denver −4.0, Detroit 0.2, Minneapolis −14.9, Atlanta 18.8, Seattle 23.8
- ACCA – Manual J, the ANSI-recognised standard for residential heating and cooling loads
- Rechner-Portal – hot-water allowance 0.25 kW per person (DIN 4708 basis: 40 litres a day per person heated by 35 K)
- NEEP – cold-climate air-source heat pump list (output at 5 °F, 17 °F and 47 °F)
Formulas last reviewed: September 30, 2026 ·How we check our formulas